Waste Oil Heaters - SB Range with Automatic Ignition
Installation of Waste Oil Heaters
The positioning of Waste Oil Heaters in the workshop must take into account the following factors: a) power supply 220/240 volt (SB40/60) 400 V + N (SB80/110)
b) Flue pipe installation
c) Air supply to main ventilator
d) Connection to a compressed air supply.
e) Access to “Day” fuel tank
Control Thermostat and Waste Oil Heaters
This multifunctional thermostat ensures that the main fan only starts after the combustion chamber has been sufficiently heated. Therefore, there is no cold air blown before heater operation.
Multi Fuel Capability
These Waste Oil Heaters operate efficiently on a general mixture of used oil. Alternatively they can be run on diesel oil, or heating oil only. The air pressure to the burner has to be adjusted. Transformer oil, petro chemical based oil, or used cutting and grinding oil must NOT be used.
Combustion Control
The burner is equipped with a photocell that continuously monitors the flame.
In case of ignition failure or poor combustion, lack of a flame or partly blocked nozzle, the photocell stops the burner.
Waste Oil Heaters Built In Room Thermostat
This thermostat enables automatic operation of the heater in order to obtain the desired room temperature and on a low position is extremely useful for overnight frost protection.
Waste Oil Heaters are supplied with a basic room thermostat. An optional digital thermostat/timer control is available at an additional cost.
Indicator Lights on Waste Oil Heaters
Waste Oil Heaters have the following lights to show you:
- when there is power to the heater
- when the main fan is operating
- when there is a burner failure
1 and 2 are positioned on the front panel of the heater. 3 is positioned on the burner control box on top of the burner.
Service and Maintenance of Waste Oil Heaters
The design of Waste Oil Heaters ensures a minimum of necessary service and the service functions can be undertaken by the owner without special tools. The complete burner unit can be removed for any maintenance and service.
Overload Protection
- Electrical overload is protected by a trip system for both the main fan and the burner
- Heating overload is protected by a limit thermostat built into a Waste Oil Heaters control thermostat. This has an automatic reset.
- Any obstruction of the main fan or its air stream is secured by a manually reset overload protection
Ventilation Only
In summertime the heater can be used for ventilation only.
Ventilation air flow rates:
SB40 – 3200m3/hr (1882cfm)
SB60 – 4100m3/hr (2412cfm)
SB80 – 6200m3/hr (3647cfm)
SB110 – 8100m3/hr (4765cfm)
Waste Oil Heaters Automatic Fuel Pre-heating (on used oil)
This system is activated when the heater is operated on used oil.
The pre-heater is then maintained at 70°C to 85°C controlled by a thermostat.
Non Return Valve
The non return valve in the fuel intake ensures that the burner cannot drain when it is not in operation.
Used Oil Compatibility with Waste Oil Heaters
The complete burner is fully automatic including the oil pre-heating system that ensures correct ignition and atomisation.
At required points, condensate drain valves are built into the system.
Flue PipeThe standard flue kit consists of:-
1 x T Piece complete with Draught Stabiliser
4 x 1m lengths of Flue Piping
1 x Terminal Pipe
These items ensure the minimum height for efficient operation, ie 6 metres above ground level and 1 metre above the roof apex.
Supports
Wall bands are available to suit the Flues and for wall fixed installation should be located at 3 metre centres.
A Guy Wire fixing bracket is available to provide extra lateral support where the flue extends more than 1.5m above the last wall band, or for inter-connection with the roof flashing.
Roof penetrations
Flat and angled flashings of sheet aluminium are available to provide suitable weather cover where the flue penetrates a roof. Silicone rubber flashings are also available and highly recommended.
Storm collars of aluminium are also available and should be fitted to the pipe immediately above the flashings.
Terminations
To prevent leakage of rainwater into the pipe at joints which may be exposed above roof level, a change-over section is supplied in the flue kit. This section of pipe is provided with a male crimped coupling at each end and is designed for use where the flue passes through the roof: one end should be installed inside the building and one outside. Any subsequent components are installed inverted, i.e. with the male coupling upwards and fitted and secured in the normal way.
Rain caps are not permitted with used Waste Oil Heaters. The terminal pipe is designed to deflect rain water down the outer section.
NB. All lengths and fittings are fabricated from 0.55mm type 430 Stainless Steel.
A Detailed instruction and service manual is supplied with all our every Waste Oil Heaters
The environmental Protection Act 1990 Part 1.
On 1 st January 1991 the Environmental Protection Act came into force introducing new controls over air pollution and included provisions to cover used oil or recovered oil burners. Used oil heaters should not be operated until they have been registered with the relevant local authority. Application Forms are available from your local District or Borough Council. “Local Authorities are expected to determine applications for new appliances within 2 weeks of receipt.”
Individual Flue Components
Straight Lengths - Fixed straight lengths are available in two sizes:- 500mm, 1000mm and Adjustable.

Fixings

Change-Over Lengths (installed through roof)

Fittings

Flashings & Terminations

| Part No. | Description |
|---|---|
| Individual Flue Components for model SB40 | |
| 41.900.821 | Flue Pipe, 1 metre x150mm |
| 41.900.822 | Flue Pipe, ½ metre x 150mm |
| 41.900.818 | Flue Pipe Adjustable (540mm to 900mm x 150mm) |
| 41.900.871 | Terminal Pipe, 1 metre x 150mm |
| 41.900.820 | Changeover Pipe, 1 metre x 150mm |
| 98.085.738 | T-Piece & Draught Stabiliser & Condensation Trap & Adaptor |
| 41.900.825 | Flue Bend, 45° x 150 mm |
| 41.900.834 | Wall Band for 150mm Flue Stack (locate at 3m centres) |
| 41.900.857 | Guy Wire bracket 150mm |
| 41.900.865 | Angled Roof Flashing 150mm – Sheet Aluminium |
| 41.900.866 | Flat Roof Flashing 150mm – Sheet Aluminium |
| 41.900.860 | Storm Collar 150mm |
| Individual Flue Components for models SB60, 80 and 110 | |
| 41.910.212 | Flue Pipe, 1 metre x 200mm |
| 41.910.215 | Flue Pipe, ½ metre x 200mm |
| 41.910.230 | Flue Pipe Adjustable (540mm to 900mm x 200mm) |
| 41.910.234 | Terminal Pipe, 1 metre x200mm |
| 41.910.214 | Changeover Pipe, 1 metre x 200mm |
| 41.910.229 | Flue Bend, 45° x 200mm |
| 41.910.204 | T-Piece & Draught Stabiliser & Condensation Trap (except SB60) |
| 98.085.104 | T-Piece & Draught Stabiliser & Condensation Trap (SB60) |
| 41.910.221 | Wall Band for 200mm Flue Stack (locate at 3m centres) |
| 41.910.206 | Guy Wire bracket 200mm |
| 41.910.207 | Angled Roof Flashing 200mm – Sheet Aluminium |
| 41.910.208 | Flat Roof Flashing 200mm – Sheet Aluminium |
| 41.910.209 | Storm Collar 200mm |
| Waste Oil Heaters Extras | |
| 40.000.238 | Draught Stabiliser (supplied with T-Piece assembly) |
| 41.900.868 | Silicone Rubber Flexible Roof Flashing 150mm |
| 98.085.497 | Silicone Rubber Flexible Roof Flashing 200mm |
| 41.900.869 | Silicone Rubber Fixing Kit for Flashing |

|
Waste Oil Heaters OVERALL DIMENSIONS (mm) |
Waste Oil Heaters TECHNICAL INFORMATION |
|||||||||
|
MODEL |
WIDTH |
LENGTH |
HEIGHT |
MODEL |
HEAT OUTPUT NETT MAX (BTU/HR) |
HEATED AIR FLOW (M3/HR) |
ELECTRIC SUPPLY (VOLTS) |
POWER CONSUMPTION (KW) |
DAY TANK CAPACITY (LITRES) |
APPROX FUEL CONSUMPTION (LITRES/HR) |
|
SB40 |
690 |
1860 |
1850 |
SB40 |
140,000 |
3200 |
230 |
1,1 |
80 |
4.5 |
|
SB60 |
690 |
1860 |
1850 |
SB60 |
180,000 |
4100 |
230 |
1,4 |
80 |
6.0 |
|
SB80 |
900 |
2060 |
2175 |
SB80 |
270,000 |
6200 |
400 + 0 |
1,8 |
130 |
9.0 |
|
SB110 |
900 |
2060 |
2175 |
SB110 |
390,000 |
8100 |
400 + 0 |
2,2 |
130 |
12.8 |
|
Model |
A |
B |
C |
D |
E |
F |
G |
H |
I |
L |
N |
Q |
R |
DIA |
WEIGHT KG |
|
SB40/60
|
570 |
910 |
1425 |
400 |
270
|
560 |
120 |
1255 |
805 |
550 |
25 |
400 |
405 |
160 |
180 |
|
SB80/110
|
760 |
1110 |
1750 |
400 |
320 |
760 |
140 |
1525 |
945 |
550 |
25 |
400 |
405 |
180 |
290 |
Accessories
Flowmatic:
An automatic motor and pump system to keep the “Day oil tank” supplied from a bulk storage tank (pipework and electric cable not included). Maximum distance 25 metres.
For longer distances a pneumatic pump system is available to special order.
Thermostat/Timer ECO.X TFP2
An energy management computer specifically designed for total space heating control.
Features of the ECO.X TFP2
• Quartz accuracy
• 7 day temperature control with each day having independent settings