OUH OIL FIRED UNIT HEATERS


Find out further information & view the full product specification

Download Brochure

OUH OIL FIRED UNIT HEATERS

Indirect oil fired suspended warm air heaters with a stainless steel heat exchanger as standard and a downwards high/low firing pressure jet oil burner, available in 4 models with outputs ranging from 20 kW to 60 kW. Designed for use in factory or warehouse premises where oil firing is a requirement and floor space is at a premium.

Models Available

  • OUH F - Freeblowing Oil Unit Heater.
  • OUH C - Centrifugal Oil Unit Heater.
  • OUH D - Ducted Oil Unit Heater.

Features

  • Proven design and years of longevity make the OUH a leading recommendation for the HVAC installer, with simple maintenance access and ease of installation for buildings where only oil is available.
  • Meets the latest ErP requirements for reduced NOx and increased seasonal efficiency, utilising state of the art burners, air movement and control technology whilst maintaining the temperature rises required in cabinet heater installations.
  • Axial fan (OUH F) models are fitted with a single fan set and discharge warmed air directly into the heated space via adjustable horizontal louvres, with vertical louvres available as an option where lateral air discharge is required.
  • Centrifugal fan (OUH C) models benefit from a close coupled fan which discharges warmed air via a duct outlet spigot suitable for the onward connection of ductwork.

Specification

  • Type tested and CE approved. Heaters made available to the market from September 2018 onwards comply with the requirements of Directive 2009/125/EC - Lot 21 Tier 1.
  • Robust and proven heat exchanger manufactured as standard from 304 grade stainless steel and lifecycle tested to ensure long service life.
  • Fitted as standard with a pre-fitted and tested low NOx, high-low control "Gulliver" burner from market-leading burner manufacturer Riello.

Technical Specifications


Model OUH 20 OUH 30 OUH 45 OUH 60
Output, high fire (max) 20 kW 30 kW 45 kW 60 kW
Output, low fire (min) 16 kW 24 kW 34 kW 45 kW
Airflow volume (OUH F) 0.7 m³/s 0.82 m³/s 1.19 m³/s 1.94 m³/s
Airflow volume (OUH C) 1 m³/s 0.82 m³/s 1.19 m³/s 1.88 m³/s
Airflow throw (OUH F) 8.5 m 16 m 25 m 34 m
Fan static pressure (OUH C) 275 Pa 305 Pa 275 Pa 384 Pa
Electrical supply, standard 230/1/50 V/ph/Hz 230/1/50 V/ph/Hz 230/1/50 V/ph/Hz 230/1/50 V/ph/Hz
Electrical supply, optional 415/3/50 V/ph/Hz 415/3/50 V/ph/Hz 415/3/50 V/ph/Hz 415/3/50 V/ph/Hz
Run current (OUH F) 0.94 A 0.46 A 0.48 A 1.7 A
Run current (OUH C) 4.3 A 4.33 A 5.54 A 8 A
Fuel oil connection ¼ BSP/Rc ¼ BSP/Rc ¼ BSP/Rc ¼ BSP/Rc
Fuel consumption 2.18 l/h 3.18 l/h 5.32 l/h 6.7 l/h
Mounting height, min (OUH F) 2.5 m 2.5 m 3 m 3 m
Mounting height, max (OUH F) 3 m 3 m 5 m 5 m
Height 806 mm 1043 mm 1049 mm 1049 mm
Width 555 mm 780 mm 780 mm 780 mm
Depth (OUH F) 868 mm 1106 mm 1115 mm 1150 mm
Depth (OUH C) 1163 mm 1470 mm 1469 mm 1469 mm
Installation clearance, top 1000 mm 1000 mm 1000 mm 1000 mm
Installation clearance, side 500 mm 500 mm 500 mm 500 mm
Installation clearance, rear 400 mm 400 mm 400 mm 400 mm
Flue diameter Ø100 mm Ø125 mm Ø125 mm Ø125 mm
Combustion air spigot Ø150 mm Ø150 mm Ø150 mm Ø150 mm
Maximum combustion duct length 120 m 100 m 81 m 21 m
Noise level (OUH F) 46 dB(A) 54 dB(A) 52 dB(A) 53 dB(A)
Nett weight (OUH F) 53 kg 126 kg 126 kg 126 kg
Nett weight (OUH C) 91.5 kg 142 kg 142 kg 142 kg

Call us on 02476 357960 or enquire about our services